Skip to main content
risertools

Spec Comparison Matrices

Side-by-side spec comparisons for low-voltage and ICT design — copper categories, fiber grades, Power over Ethernet, surveillance procurement, and UPS form factors — each anchored to its published source.

Twisted-pair copper categories — channel reach, 10GBASE-T, bandwidth, and PoE[1][2]

Twisted-pair copper categories — channel reach, 10GBASE-T, bandwidth, and PoE
CategoryChannel limit10GBASE-T reachBandwidthPoE (802.3bt)
Cat 5e100 mNot rated100 MHzType 1–4
Cat 6100 m37–55 m250 MHzType 1–4
Cat 6A100 m100 m500 MHzType 1–4
Cat 830 m30 m2000 MHzType 1–4

Optical fiber grades — 10G/40G/100G reach, core diameter, and mode[3][2]

Optical fiber grades — 10G/40G/100G reach, core diameter, and mode
Fiber10G reach40G reach100G reachCoreMode
OM3300 m100 m70 m50 µmMultimode
OM4400 m150 m100 m50 µmMultimode
OM5400 m150 m100 m50 µmMultimode
OS210 km10 km10 km9 µmSinglemode

Power over Ethernet types — IEEE 802.3 power budget and pair count[2]

Power over Ethernet types — IEEE 802.3 power budget and pair count
Type (clause)W at PSEW at PDPairs
Type 1 (802.3af)15.4 W12.95 W2
Type 2 (802.3at)30 W25.5 W2
Type 3 (802.3bt)60 W51 W4
Type 4 (802.3bt)90 W71.3 W4

Surveillance procurement under NDAA §889 — statutory categories and federal eligibility[4]

Surveillance procurement under NDAA §889 — statutory categories and federal eligibility
Equipment category (§889)Federal procurement statusBasis
Equipment from §889(f)(3) covered entities§889-restrictedStatute names Huawei, ZTE, Hytera, Hikvision, Dahua
Compliant non-covered video-surveillance equipmentCompliantNot a covered entity under §889(f)(3)
Components incorporating covered telecommunications equipment§889-restricted"Substantial or essential component" clause, §889(f)(2)–(3)

UPS form factors — typical capacity, runtime posture, and deployment[5]

UPS form factors — typical capacity, runtime posture, and deployment
Form factorTypical capacityRuntime postureUse-case
Tower500–3000 VAFixed internal batteryWorkstation, edge closet
Rackmount1000–10000 VAInternal plus external packsServer rack, IDF/MDF
Modular10000–50000 VAScalable hot-swap modulesData-center power room

References

  1. ANSI/TIA-568.2-E — Balanced Twisted-Pair Telecommunications Cabling and Components Standard (2024)

    Defines the balanced twisted-pair category channel reach (100 m for Cat 5e/6/6A, 30 m for the Cat 8 data-center channel) and the tested bandwidth per category. (paraphrase)

    Last verified: 2026-06-14. View on TIA store →

  2. IEEE Std 802.3 — IEEE Standard for Ethernet

    Specifies the 10GBASE-T copper reach, the multimode SR application distances, and the Power over Ethernet Type 1–4 powered-device classes (802.3af/at/bt) — the power budget per type and pair count. (paraphrase)

    Last verified: 2026-06-14. View on IEEE store →

  3. ANSI/TIA-568.3-E — Optical Fiber Cabling and Components Standard (2022)

    Specifies the optical-fiber grades (OM3/OM4/OM5 multimode at 50 µm core, OS2 singlemode) and the cabling-component performance the application reach budgets rest on. (paraphrase)

    Last verified: 2026-06-14. View on TIA store →

  4. National Defense Authorization Act for Fiscal Year 2019, Section 889 — Prohibition on Certain Telecommunications and Video Surveillance Equipment

    Prohibits federal agencies from procuring covered telecommunications and video-surveillance equipment from the entities the statute names in §889(f)(3) — a federal sourcing constraint, not an industry standard. (paraphrase)

    Last verified: 2026-06-14. View the statute text →

  5. IEC 62040-3 — Uninterruptible Power Systems (UPS) — Part 3: Method of specifying the performance and test requirements

    Defines the UPS output power rating (VA / W) and the stored-energy runtime characterization that frames the tower / rackmount / modular form-factor capacity bands. (paraphrase)

    Last verified: 2026-06-14. View on IEC store →